Fire extinguisher op 5 technical specifications gost. How to receive the ordered goods or delivery methods

Complies with GOST R 51057-2001 " Fire fighting equipment. Fire extinguishers are portable. General technical requirements. Test Methods"

It is one of the most common fire extinguishers due to the optimal combination of size, weight and fire extinguishing ability. This fire extinguisher can be used by almost all categories of the population, this is especially true when there is a shortage of male personnel.

Designed for use:

  • on passenger vehicles - 1 pc, on freight, passenger vehicles - 2 pcs;
  • in public, warehouse and industrial premises at the rate of one fire extinguisher per 100 m 2 area, but not less than two

Specifications:

  • charge mass - 5 kg;
  • working pressure - 1.4 MPa;
  • jet length - 3 m;
  • the duration of the supply of fire extinguishing agent - 10 s;
  • fire extinguishing capacity 2A (extinguishing a stack of 112 wooden bars 635 * 40 * 40 mm), 70V (extinguishing gasoline on an area of ​​​​2.25 m 2);
  • overall dimensions - height 466 mm, case diameter 157 mm;
  • fire extinguisher weight - no more than 7.7 kg;
  • temperature regime of storage and use - from -40 to +50 °С.
  • Service life 10 years

Maintenance:

During the operation of the fire extinguisher, it is necessary to carry out its timely maintenance at specialized stations, in the amount of:

  • re-examination (checking parameters) - annually;
  • recharge - 1 time in five years, after use, when pressure drops;
  • fire extinguishers installed on vehicles must be recharged at least once every 24 months;
  • fire extinguishers mounted on vehicles outside the cab or interior and exposed to adverse climatic and physical factors, must be recharged at least once every 12 months.

Accommodation:

On vehicles, fire extinguishers must be located in the cab, in close proximity to the driver or in a place easily accessible to him. Do not store fire extinguishers inplaces, access to which is difficult (trunk, body, etc.).

In buildings, a fire extinguisher is located near the places of the most likely occurrence of a fire, along evacuation routes, and also near the exit from the premises. in such a way that it is protected from direct sunlight, heat fluxes, mechanical influences and other adverse factors. Need to ensuregood visibility and easy access in case of fire.

Typically, a fire extinguisher is hung on a bracket, while the top of the fire extinguisher should be located at a height of no more than 1.5 m from the floor. It is also possible to installin a fire cabinet or on a special stand.

Usage:

To use a fire extinguisher, you need to follow these simple steps:

  1. Pull out the pin by the ring, which prevents the fire extinguisher from accidentally working, while the safety seal is broken;
  2. Point the hose socket at the fire site and press the lever.

Extinguishing methods:


Certificate





Description Yarpozhinvest OP-5

Powder fire extinguishers Yarpozhinvest OP-5 with a mass of fire extinguishing agent of 5 kg are designed (depending on the type of charged powder) to eliminate fires of solid substances, mainly of organic origin (class A); fires of flammable liquids or consumable solids (class B); fires of gaseous substances (class C), as well as fires of electrical equipment energized no more than 1000 V (class E fire), when operating in a temperate climate U, category 2, atmosphere type II according to GOST 15150.

Fire extinguishers Yarpozhinvest OP-5 are not designed to extinguish fires of alkali and alkaline earth metals and other materials, the combustion of which can occur without air access.

Fire extinguishers Yarpozhinvest OP-5 are reusable products.

Specifications Yarpozhinvest OP-5

  • Unit: 1 piece
  • Dimensions (mm): 157x157x466
  • Weight (kg): 5.00
  • Fire class ABCE
  • Weight of powder charge, kg, not less than 5±0.25
  • Working pressure, MPa 1.4±0.2
  • Jet length, m 3
  • Duration of OTV supply, s, not less than 10
  • Fire extinguishing capacity by fire class:
    - model fire class A 2 A
    - model hearth class B 70V
  • Service life of a fire extinguisher, years 10
  • Overall dimensions, mm: - height 466 - diameter 157
  • Displacement gas Air
  • Re-examination at least once every 5 years
  • Operating temperature range, °С - 50…+50

Fire is the most destructive element, which in a matter of minutes can destroy a building of a fairly large scale. That is why every person should always have a means of protection against it at hand. These include the OP-5 fire extinguisher, which can easily cope with a starting fire.

Description

Powder fire extinguisher OP-5 is designed to extinguish initial fires. Its charge mass is 6 kg, and the ejection length is 3.5 m. The device itself weighs 7 kg 900 g. This device is recommended to be used when extinguishing fires of liquid, solid, gaseous substances and electrical installations with voltage up to 1000 V. This device is usually equipped with cars , agricultural machinery, chemical facilities, workshops, garages, shops, offices, warehouses and even apartments. In the event of a fire in equipment, the OP-5 fire extinguisher should never be used, since if the powder gets in, it can fail, without the possibility of further recovery.

How to operate a fire extinguisher?

In order for the OP-5 to always be in working condition, careful care is required for it. To do this, it will be necessary to check the compliance of the gas pressure value and its set parameter on the manometer of the device once every 3 months. In this case, the indicator arrow should be set on a green scale, which will mean the suitability of the device for work. If the arrow of the pressure gauge is on the red scale, then this will tell you about the required one, which is carried out in a specialized office.

Advantages of powder fire extinguisher OP-5

  1. The characteristic of the OP-5 fire extinguisher tells the user that this device has a long service life - 10 years. But at the same time, it must be re-examined once every 5 years.
  2. The OP-5 fire extinguisher is equipped with a pressure indicator, which will allow the user to visually check the unit's performance.
  3. Due to the presence of a valve built into the head of the unit, the user, if desired, will be able to batch release the powder substance.
  4. The OP-5 fire extinguisher has a built-in check that protects the device from spontaneous operation.
  5. The performance of the device does not depend on temperature (it is used from -60 C to + 50 C).
  6. Quick actuation of the device (3 seconds is enough).
  7. Attractive price (depending on the area, the cost of the product varies from 350 to 600 rubles).

Disadvantages of powder fire extinguisher OP-5

  1. Low visibility when extinguishing fires, due to the high dust content of the space from the formed powder cloud.
  2. It is impossible to use the OP-5 fire extinguisher to protect equipment.
  3. The device does not have a cooling effect. Given this circumstance, it is possible that the extinguished surface will re-ignite.

Well, whether or not to buy an OP-5 fire extinguisher is up to you. But remember, if the device will hang on the wall in the future, then do not forget to purchase an additional bracket.

The OP-5 fire extinguisher belongs to the portable powder fire extinguishers of the injection type.Powder fire extinguisher OP-5is the primary fire extinguishing agent and is designed to extinguish fire in case of ignition of gaseous, liquid and solid substances. It can also be used to eliminate the ignition of electrical installations that are energized up to 1000 V. It is an essential attribute of vehicles. It is intended for their complete set according to rules of fire safety. It is ideal for a car.

INDOOR USE AND PLACEMENT OF POWDER FIRE EXTINGUISHER OP-5

Powder fire extinguisher OP-5 should be located in such a way that they are protected from direct sunlight, heat fluxes, mechanical stress and other adverse factors (vibration, aggressive environment, high humidity, etc.). They must be clearly visible and easily accessible in the event of a fire. It is preferable to place fire extinguishers near the places of the most probable fire, along the paths of passage, and also near the exit from the premises. Fire extinguishers should not impede the evacuation of people during a fire. To accommodate primary fire extinguishing equipment in production and storage facilities, as well as on the territory of protected facilities, fire shields (points) must be equipped. In rooms saturated with industrial or other equipment that obscure fire extinguishers, signs and signs of their location should be installed. Pointers must be made in accordance with GOST 12.4.026 and located in prominent places at a height of 2.0 - 2.5 m from the floor level, taking into account the conditions of their visibility [GOST 12.4.009; 4] The distance from a possible source of fire to the nearest powder fire extinguisher should not exceed 20 m for public buildings and structures; 30 m for rooms of categories A, B and C; 40 m - for rooms of categories C and D; 70 m - for rooms of category D.

Recommended powder fire extinguisher OP-5 install on hanging brackets or in special cabinets and stands. Powder fire extinguisher OP-5 should be located so that the main inscriptions and pictograms showing the order of putting them into action are clearly visible and facing outward or in the direction of the most likely approach to them.

Locking and starting device and cabinet doors (if they are placed in the cabinet) must be sealed

Powder fire extinguisher OP-5 must be installed in such a way that their top is located at a height of not more than 1.5 m from the floor. They can be installed on the floor, with mandatory fixation from a possible fall due to accidental impact.

Distance from door to powder fire extinguisher OP-5 should be such as not to interfere with its full opening.

Powder fire extinguishers OP-5 should not be installed in places where temperatures are outside the temperature range indicated on the fire extinguishers.

The use of primary fire extinguishing equipment for household and other needs not related to fire extinguishing is not allowed.

Standards for equipping premises with a powder fire extinguisher OP-5

Maximum protected area, m 2

Fire class

Powder fire extinguisher OP-5

A B C

(combustible gases and liquids)

G, D

1800

Public buildings

Notes.

1. To extinguish fires of various classes, powder fire extinguishers must have the appropriate charges: for class A - powder type ABCE, for classes B, C and E - type ALL or ABCE, and for class D - type D

2. The ++ sign indicates fire extinguishers recommended for equipping objects, the + sign indicates fire extinguishers, the use of which is allowed in the absence of recommended ones or with appropriate justification, the sign - fire extinguishers that are not allowed for equipping these objects.

For the maximum area of ​​premises of different categories (the maximum area protected by one or a group of fire extinguishers), it is necessary to provide for the number of fire extinguishers of one of the types indicated in Table. 1 or 2 before the ++ or + sign.

USE AND PLACEMENT OF POWDER FIRE EXTINGUISHER OP-5 ON VEHICLES

For the protection of vehicles, powder fire extinguishers.

It is allowed to install only those fire extinguishers on motor vehicles, the design of which has passed the vibration test.

As a charge in powder fire extinguishers, it is advisable to use multi-purpose powder compositions of the ABCE type.

Cars and trucks must be equipped with powder fire extinguishers with a housing capacity of at least 2 liters (type OP-2).

Buses of a particularly small class (such as RAF, Gazelle, etc.) are equipped with at least one fire extinguisher of the type OP-2;

small class buses (PAZ, etc.) - two fire extinguishers OP-2, buses of the middle class (LAZ, LiAZ, etc.) and other vehicles for transporting people - with two fire extinguishers (one in the OP-5 cab, the other in the cabin OP-2).

Tank trucks for the transportation of petroleum products and vehicles for the transportation of dangerous goods must be equipped with at least two fire extinguishers of the OP-5 type: one must be located on the chassis, and the second - on the tank or in the body with the load.

Heavy off-road dump trucks must be equipped with one fire extinguisher of type OP-5.

Mobile laboratories, workshops and other vehicles such as a van mounted on a car chassis must be equipped with two-liter fire extinguishers of the appropriate type, depending on the class of possible fire and the features of the mounted equipment.

On all vehicles, fire extinguishers must be located in the cab, in close proximity to the driver or in an easily accessible place. It is forbidden to store fire extinguishers in the trunk, body or in other places that are difficult to access. Fire extinguishers located outside the cab should be protected from rain, sunlight and dirt.

The design of the bracket must be reliable in order to exclude the possibility of the fire extinguisher falling out of it when the car is moving, as well as in the event of a collision or hitting it against an obstacle.

MAINTENANCE AND PERIODIC CHECKS OF THE POWDER FIRE EXTINGUISHER OP-5

Powder fire extinguisher OP-5 put into operation, must be subjected to maintenance, which ensures the maintenance of the fire extinguisher in constant readiness for use and the reliable operation of all components of the fire extinguisher during the entire period of operation.

Maintenance includes periodic checks, inspections, repairs, testing and recharging of fire extinguishers.

Periodic checks are necessary to monitor the condition powder fire extinguisher OP-5, control of the place of installation of the fire extinguisher and the reliability of its fastening, the possibility of a free approach to it, the presence, location and readability of the instructions for working with the fire extinguisher.

Maintenance powder fire extinguisher OP-5 should be carried out in accordance with the operating instructions and using the necessary tools and materials by a person appointed by order of the enterprise or organization, who has passed, in the prescribed manner, the knowledge of regulatory and technical documents on the design and operation of fire extinguishers and the parameters of fire extinguishers, who is able to independently carry out the necessary amount of work on maintenance of fire extinguishers.

Powder fire extinguishers OP-5, taken out of service for the period of repair, testing or recharging, must be replaced by backup fire extinguishers with similar parameters.

Before the introduction powder fire extinguisher OP-5 into operation, it must be subjected to an initial check, during which an external inspection is carried out, the complete set of the fire extinguisher and the condition of the place of its installation (the visibility of the fire extinguisher or the indicator of the place of its installation, the possibility of a free approach to it), as well as the readability and intelligibility of the instructions for working with the fire extinguisher . During the external inspection, attention should be paid to:

The presence of dents, chips, deep scratches on the body, control units, nuts and fire extinguisher head;

Condition of protective and paint coatings;

Clear and understandable instructions;

The presence of a sealed safety device;

The serviceability of the pressure gauge or pressure indicator (if it is provided for by the design of the fire extinguisher), the presence of the necessary brand and the pressure in the fire extinguisher of the injection type or in the gas cylinder;

The mass of the fire extinguisher, as well as the mass of the fire extinguisher in the fire extinguisher (the latter is determined by calculation);

The condition of the flexible hose (if any) and the OTV sprayer (the presence of mechanical damage, traces of corrosion, casting flash or other objects that prevent the free exit of the OTV from the fire extinguisher);

The condition of the running gear and the reliability of fastening the fire extinguisher body on a trolley (for a mobile fire extinguisher), on a wall or in a fire cabinet (for a portable fire extinguisher).

Based on the results of the check, the necessary marks are made in the fire extinguisher's passport, it is assigned a serial number, which is applied to the fire extinguisher and recorded in the fire extinguisher register.

Quarterly inspection includes inspection of the installation site powder fire extinguisher OP-5 and approaches to it, as well as conducting an external inspection of the fire extinguisher.

The annual inspection of the fire extinguisher includes an external inspection powder fire extinguisher OP-5, inspection of the place of its installation and approaches to it. During the annual inspection, the amount of leakage of propellant gas from a gas cylinder or OTV from a gas fire extinguisher is monitored. The fire extinguishers are opened (full or selective), the condition of the filters is assessed, the parameters of the fire extinguisher are checked and, if they do not meet the requirements of the relevant regulatory documents, the fire extinguishers are recharged.

In case of increased fire hazard of an object (rooms of category A) or when exposed to powder fire extinguisher OP-5 such unfavorable factors as positive (above 40 °C) or negative (below minus 40 °C) ambient temperature close to the limit value, air humidity over 90% (at 25 °C), corrosive environment, exposure to vibration, etc. etc., checking of fire extinguishers and control of fire extinguishers should be carried out at least once every 6 months.

If during the check a discrepancy is found in any parameter powder fire extinguisher OP-5 the requirements of the current regulatory documents, it is necessary to eliminate the causes of the identified deviations of the parameters and recharge the fire extinguishers.

At least once every 5 years powder fire extinguisher OP-5 and the expellant gas cylinder must be discharged, the fire extinguisher body must be completely cleaned of the remnants of the fire extinguishing agent, external and internal inspections, as well as hydraulic strength testing and pneumatic testing for tightness of the fire extinguisher body, starting head, hose and locking device, have been carried out. During the inspection, attention should be paid to:

The condition of the inner surface of the fire extinguisher body (the presence of dents or blisters in the metal, peeling of the protective coating);

The presence of traces of corrosion;

Condition of gaskets, cuffs or other types of seals;

The condition of safety devices, filters, pressure measuring instruments, reducers, valves, locking devices and their seats;

The mass of the gas cartridge, the period of its next test or the period of warranty operation of the gas generating element;

Surface condition and hose attachment points;

Condition, warranty period of storage and values ​​of the main parameters of OTV;

The condition and tightness of the container for surfactant or foam concentrate (for water and foam fire extinguishers with separate storage of water and other charge components).

In case of detection of mechanical damage or traces of corrosion, the body and components of the OP-5 powder fire extinguisher must be subjected to a strength test ahead of schedule.

The checks and tests carried out are noted on the OP-5 powder fire extinguisher, in its passport and in the register of fire extinguishers.

Operational certificate for a fire extinguisher

1. Number assigned to the fire extinguisher

2. Date of commissioning of the fire extinguisher

3. Installation location of the fire extinguisher

4. Type and brand of fire extinguisher

5. Fire extinguisher manufacturer

6. Serial number

7. Date of manufacture of the fire extinguisher

8. Brand (concentration) of charged OTV

Fire Extinguisher Maintenance Results

Date and type of maintenance performed

Appearance and condition of fire extinguisher components

Full mass of fire sewer

Pressure (if equipped with a pressure indicator) * or weight of the gas bottle

State of the running gear of a mobile fire extinguisher

Measures taken to eliminate the noted shortcomings

Position, surname, initials and signature of the responsible person

Fire Extinguisher Maintenance Log

No. and

Maintenance (type and date)

Remarks

about technical

able

Taken measures

Job title, surname, initials and signature Wow

brand of flamethrower

Checking fire knots sewer

OTV quality check

Checking the pressure indicator

Reloading a row of fire extinguisher

Fire knot test sewer

Journal of testing and recharging fire extinguishers

N and brand of fire extinguisher

Date of testing and reloading; maintenance organization living

result inspection and testing strength test

Fires in the city of Moscow, as well as any other locality in the country, are not uncommon. The focus of fire damage can be quite harmless.

For example, a power supply that ignited from overheating or a TV that flared up due to a voltage drop.

It is to suppress a fire in a small area that the powder fire extinguisher OP-5 was developed.

This device is compact and light enough to be used by one person.

The main purpose of the fire extinguisher OP-5

Powder fire extinguisher OP-5 is quite versatile. To be sure that the device will show high efficiency, you should pay attention to the technical characteristics of the fire extinguishing agent indicated in the marking.

The designation ABCE means that the model is capable of fighting fires of the following classes:

  1. A, ignition of solids and mixed materials;
  2. B, burning liquids;
  3. C, ignition of gases;
  4. E, fire of electrical installations under voltage.

A fire extinguisher should be used only in cases where the duration of the ejection of the jet and the equipment of the model with a charge are capable of extinguishing the fire. Also, the fire extinguishing ability of the device will be zero if it is used to process substances that do not require oxygen for combustion. These include, for example, alkali metals and some acids.

To get at your disposal a device with a quick start-up and a simple technique of use, it is worth purchasing an OP 5 Z fire extinguisher. This is a pumping type, there is gas under high pressure inside the housing cylinder.

The release of the active substance occurs almost instantly. The nature of the action of powders on the area of ​​fire damage differs from other types of working fluid used in fire extinguishers.

The principle of operation of the powder fire extinguisher OP-5

The device of the OP-5 fire extinguisher, which is a design of a vessel under pressure, implies an almost instantaneous release of a powder jet. Getting on the source of ignition, the fire extinguishing agent creates a layer that blocks the flow of oxygen.

Features of powder fire extinguishing are as follows:

  • all types of powders do not create a risk of short circuit, which is the difference between foam and aqueous solutions. OP-5 can be used to extinguish electrical installations whose operating voltage is less than 1000 V;
  • when processing with an active agent, the treatment zone does not cool, as does a carbon dioxide fire extinguisher;
  • a full assessment of the level of danger shows that OP-5 in a room of limited volume is more attractive, since the active substance cannot cause damage to the respiratory system, as does the carbon dioxide of devices of the corresponding brand.

However, the powder fire extinguisher OP-5 Z AVSE, as well as devices with other types of fire extinguishing powder, have disadvantages. One of them is a sharp drop in visibility when operating indoors. The active substance is finely dispersed, when ejected, the suspension hangs in the air.

The description of the shortcomings of the device will not be complete without mentioning the secondary damage. It is expressed in damage to trim elements, device cases that are in plain sight. The powder is able to fuse into a variety of surfaces at high temperatures in the fire. It may not be possible to remove it.

To start extinguishing a fire, a fire extinguisher must be moved to the source of ignition. To start, the seal is removed, the pin or other blocking element of the locking device is removed.

When this is done, to start the ejection of the powder jet, the block with the handle is taken all the way up and the latter is pressed. The flow of the active substance occurs all the time while the operator holds the trigger in the depressed position.

After using the downloaded OP-5, it must be recharged. Also, in order to preserve the suitability and confidence in the effectiveness of the application, you should carefully observe the storage conditions of the device, the inspection periods.

The powder fire extinguisher should be recharged at least once every 5 years, from the moment of the last calibration, regardless of the actual service life.

Device Specifications

The mass of the fire extinguisher OP-5 is a maximum of 6.8 kg in a fully equipped state.

The device must be installed in special wall brackets, its dimensions allow installation on stands or lockable cabinets.

The service life of the fire extinguisher OP 5 declared by the manufacturer is 10 years. Devices put into service - must be recharged once every 5 years. Storage of powder pump fire extinguishers is also subject to certain rules.

Products are stored and operated at temperatures from -20 to 50 degrees Celsius. When installing devices, moving, storing - it is worth considering the features of the engineering solution.

In particular, when fire extinguishers are charged, they are high-pressure gas cylinders. Deformation of the body, sharp mechanical, force impacts, falls from a height are not allowed.

Conclusion

Light weight, compactness, ease of starting operations, quick delivery of the extinguishing agent, its high versatility make the OP-5 powder fire extinguisher an extremely popular product. They are equipped with fire shields of small workshops, workshops of enterprises.

The device shows high efficiency when used in transport. Can be successfully used in offices, apartments, hotels.

Today you can buy OP 5 with different characteristics of the powder. Possibility of choice - allows you to optimize costs by carefully analyzing and predicting possible types of fires and their level of danger.

Video: Testing powder fire extinguisher OP-5 hearth 55V

Name Meaning
Fire extinguisher weight6.8 kg
Mass of charge of the active substance5 kg with an error of 250 g
Operating pressure1.4 MPa
Throw lengthat least 3 meters
Continuous blast time10 sec
Jet ejection time during operation with a series of short-term inclusionsup to 120 sec
Working temperature range-20 to 50 degrees Celsius
dimensions420x176 mm
Life time10 years